Wire & Conduit Tools
Wire Size Finder — enter load and run length; we'll recommend a conductor and auto-select it below
Conductor Selector — pick a wire size to populate all readouts and calculators below
Conversions
Area
Temperature
1 kcmil = 0.5067 mm² · type any value to see the inverse update live.
Readout for 14 AWG
Voltage Drop Calculator — for the selected conductor size 14 AWG
Cable Pulling Tension — for the selected conductor size 14 AWG
ⓘ Bend radius (NEC 300-34): nonshielded cable ≥8× cable O.D.; shielded cable ≥12× cable O.D. Sidewall pressure at bends often limits the pull before this max tension does. Typical friction: PVC dry ~0.5, PVC w/ lube ~0.2, steel dry ~0.5, steel w/ lube ~0.3.
* Per NEC 240.4(D), overcurrent protection of small conductors is limited regardless of ampacity: 14 AWG Cu → 15 A, 12 AWG Cu → 20 A, 10 AWG Cu → 30 A (12 AWG Al → 15 A, 10 AWG Al → 25 A).
Ampacity values from 2023 NEC Table 310.16, based on 30°C ambient and not more than three current-carrying conductors in a raceway. Conduit sizes assume a 3-conductor install; for other fill conditions consult NEC Chapter 9, Tables 4 & 5.
Copper weights are bare ASTM B8 concentric-lay-stranded conductors. Aluminum weights are bare ASTM B231 (AAC 1350) concentric-lay-stranded; smaller sizes (8 AWG and below) are not standardly tabulated as AAC and are shown as —.
Voltage-drop values are volts per amp per 100 ft of copper run at 0.8 power factor; the 1Φ value already accounts for round-trip distance.